Thermocouple Extension Cables |
| |
|
300 Volt Thermoplastic PVC |
| |
|
|
|

|
 |
Applications |
UL listed as PLTC
NEC
Article 725
Suitable for
Class I, Division 2 and Class II, Division
2 hazardous areas
300 volt
rated insulation
Description
Conductor..........................
Solid alloy wire
Primary
insulation.............. 15 mils (0.4
mm) 105 °C PVC
Color code.........................
ANSI standard
Pair shield..........................
(Type 1802 / 1824) 100% coverage, an
aluminum-polyester tape shield and
a solid, tinned copper drain wire
Overall
shield..................... (Type 1820
/ 1824) 100% coverage, an aluminum-polyester
tape shield and a 7-strand tinned copper
drain wire
Jacket.................................
FR-PVC, ANSI colour-coded
Communication wire ...........
(Type 1820 / 1824) 22-AWG copper, color-coded
orange
Bending Radius
6
x d (d = overall diameter)
Cable Type
1800
Single pair unshielded
1802
Single pair shielded
1820
Multiple pair overall shield
1824
Multiple pair individual and overall
shield
Other Options
Manufactured
in accordance with UL. Also available
to ICEA, IEC, BS standards or customized
configurations.
Various
metric and AWG size conductors
Special
color coding of insulation and jacket
materials
The specifications listed
above are subject to change without
notice. In any change, the product's
performance will remain the same, or
be improved
|
 |
COMPENSATING AND EXTENSION
CABLES INSULATED WITH PVC
Flexible conductors insulated with
PVC, flame resistant HT 150° C External
sheath in flame resistant PVC HT 150°C

OVAL SHAPE
COMPENSATING AND EXTENSION
CABLES INSULATED WITH SILICONE RUBBER
Flexible conductors insulated with
silicone rubber External sheath in
silicone rubber + 180°C

OVAL SHAPE
Additional steel braid protective
jacket
COMPENSATING AND EXTENSION
CABLES INSULATED WITH FIBREGLASS
Flexible conductors insulated with
fibreglass or silicone External sheath
in fibreglass + 250°C

OVAL
SHAPE
Insulation of single conductors
in fibreglass
Parallel cores Fibreglass
braid jacket
External screening tin-plated
copper braid jacket
|
 |
Technical
Data
Minimum bending radius : 7.5
x Ø(CEI 11.17)
Resistance to radiations
: 8 x 10 7 KJ/kg
Temperature range :
- 25 °C +
105 °C
Insulation resistance
: > 1 M Ω /km
Beahaviour in presence of flame
: Non flame propagating, self extinguishing.
| |
|
|
P2P |
| |
Nominal
cross
section mm2 |
Number
and
diameter
of wires
mm |
Approx
outer diameter
mm |
Approx.
weight
kg/km |
1 |
2x0.22 |
7x0.20 |
4.6x2.8 |
20 |
2 |
2x0.50 |
6x0.32 |
4.8x3.1 |
30 |
3 |
2x0.80 |
10x0.32 |
5.8x3.6 |
41 |
4 |
2x1.00 |
12x0.32 |
6.2x3.7 |
49 |
5 |
2x1.30 |
16x0.32 |
6.8x4.1 |
60 |
6 |
2x1.50 |
19x0.32 |
7.0x4.3 |
69 |
|
Minimum bending radius : 7.5
x Ø(CEI 11.17)
Resistance to radiations : 2 x 10 7 KJ/kg
Temperature range : - 25 °C
+ 105 °C
Insulation resistance : > 1 M Ω /km
Beahaviour in presence of flame : Non flame propagating, self extinguishing.
Absence of halogens : In accordance with IEC 754-1 and VDE 0742 part 813
No development
of corrosive gases (CEI 20.37)
| |
|
|
S2P |
P2P |
| |
Nominal
cross
section mm2 |
Number
and
diameter of wires
mm |
Approx
outer diameter
mm |
Approx.
weight
kg/km |
Approx
outer diameter
mm |
Approx.
weight
kg/km |
1 |
2x0.22 |
7x0.20 |
4.6x2.8 |
20 |
5.8X4.0 |
28 |
3 |
2x0.80 |
10x0.32 |
5.8x3.6 |
41 |
7.1X4.7 |
52 |
6 |
2x1.50 |
19x0.32 |
7.0x4.3 |
69 |
8.2X5.4 |
85 |
|
Minimum bending radius : 7.5 x Ø(CEI
11.17)
Temperature range :
- 60°C
+
200°C
Temperature range : - 60°C
+ 250°C
Insulation resistance : > 1 M Ω /km
Beahaviour in presence of flame : Non flame propagating, self extinguishing.
Absence of halogens : In accordance with IEC 754-1 and VDE 0742 part 813
No development
of corrosive gases (CEI 20.37)
| |
|
|
S5P |
S5PA |
V1P |
| |
Nominal
cross
section mm2 |
Number
and
diameter of wires
mm |
Approx
outer diameter
mm |
Approx.
weight
kg/km |
Approx
outer diameter
mm |
Approx.
weight
kg/km |
Approx
outer diameter
mm |
Approx.
weight
kg/km |
1 |
2x0.22 |
7x0.20 |
4.1x2.4
|
18 |
4.8X3.1 |
28 |
4.1x2.6 |
24 |
2 |
2x0.50 |
6x0.32 |
- |
- |
- |
- |
4.5x2.8 |
33 |
3 |
2x0.80 |
10x0.32 |
5.2x2.8 |
32 |
5.9x3.7 |
52 |
5.0x3.0 |
39 |
4 |
2x1.00 |
12x0.32 |
- |
- |
- |
- |
5.2x3.1 |
46 |
5 |
2x1.30 |
16x0.32 |
- |
- |
- |
- |
5.6x3.3 |
55 |
6 |
2x1.50 |
19x0.32 |
5.9x3.2 |
45 |
6.6x3.9 |
75 |
5.8x3.4 |
66 |
|
| |
Rating
in accordance with
DIN
IEC 584
|
Rating in accordance
with ANSI MC 96.1 |
| - |
T |
TPX-TNX |
T |
TPX-TNX |
| JX |
J |
JPX-JNX |
J |
JPX-JNX |
| - |
K |
KPCA-KNCA |
K |
- |
| KCB |
K |
KPCB-KNCB |
K |
VPX-VNX |
| KX |
K |
KPX-KNX |
K |
KPX-KNX |
| - |
E |
EPX-ENX |
E |
EPX-ENX |
| SX
/ RX |
S
/ R |
S/RPCB-S/RNCB |
S
/ R |
S/RPX-S/RNX |
|
|
 |
Dimensions
Conductor size 0.5 mm 2 (20
AWG)
| Electrical
Properties |
Units |
Screened
and armoured |
20
AWG / .5 mm 2 |
16
AWG / 1.3 mm 2 |
| Mutual
Capacitance |
|
| Type
1800 |
pF/ft |
pF/m |
31 |
100 |
36 |
119 |
| Type
1802 |
pF/ft |
pF/m |
49 |
160 |
64 |
210 |
| Type
1820 |
pF/ft |
pF/m |
31 |
100 |
36 |
119 |
| Type
1824 |
pF/ft |
pF/m |
49 |
160 |
64 |
210 |
| Inductance
(L) |
pH/ft |
pH/m |
0.19 |
0.62 |
0.17 |
0.54 |
|
|
 |
|