RD-Y(St)Y |
Instrumentation
and control cable |
| |
|
... x 2 x 0.5 mm2 Bd
Pairs laid up in bundles |
| |
|
... x 2 x 1.0 mm2 Bd |
|

|
 |
Applications |
Installation cables with electrostatic screen (St) are used for optimum data transmission in instrumentation and control engineering for process control and computers in power plants.
Short and different pitch lengths for the pairs within a bundle guarantee good crosstalk attenuation values and ensure the transmission of analogue and digital signals up to frequencies of 10 kHz. The static screen of plastic coated metal foil protects the circuits from external electrical interference, for compliance with capacitance unbalance specifications and to assure an exact pulse transmission.
In accordance with new environmental regulations, these cables are used for control systems in fumes gas desulphurisation units in incinerators as well as for upgrading older installations of power supply companies. These data transmission cables are suitable for permanent installation in dry and moist rooms, refer also to VDE 0800 part 1.
Characteristic features
The optimised
design and construction of these
data transmission cables ensures
compatibility with the well-known
ABB control systems DECONTIC® and
PROCONTIC®.
Used
in particular in the field of industrial
electronics and power and lighting
engineering.
Special
PVC-insulation and sheath compounds
guarantee first-class mechanical
properties and high flexibility of
the cable.
0.5 mm2
: suitable for Teumi-Point wiring
due to the 7-strand wire construction.
Durability
The PVC sheath is largely resistant to oils (depending on the type of oil),
excluding VDE 0472 part 803.
Chemical resistance for PVC refer also to the Table of Technical Guidelines.
Recommended for electromagnetic compatibility
|
 |
Cable design
Construction designed on the
basis of VDE 0815 conductor :plain
Cu wires, 7-strand
Construction of the conductor: 0.5
mm2 : 7 x 0.3 mm
1.0
mm2 : 7 x 0.43 mm
Insulation : core
insulation of special PVC Compound
According
to VDE 0207 part 4
Pair : 2 cores twisted
to a pair , pitch
lengths for pairs ? 50 mm for 0.5 mm2
Core
identification: colour coded according to
VDE 0815
Pair identification : pair
1 blue/red pair
3 green/brown
pair
2 grey/yellow pair
4 white/black
Bundle : each bundle
laid up with 4 pairs open spirals
with imprinted numbers assigned to
the bundles Type
of lay-up : basic bundles laid up in
layers
Screen (St)
: static screen of plastic coated metal
foil, metal side on the inside and
1 Cu drain
wire (0.5 mm2 = 7 x 0.3
mm) under the metal foil, tinned
Sheath
: sheath material of special PVC compound
Sheath colour : grey, blue also available
(RAL 5015) **)
Sheath wall : according
to VDE 0815 for interior
Thickness
installation * )
Note
* ) for underground installation
applications, the colour is black with
a reinforced PVC outer sheath (Yv), wall
thickness according to VDE 0816, or alternatively
with an additional sheath of wall thickness
1.0 mm (YY) available upon request.
**) With blue sheath for intrinsically
safe systems available upon request.
Note
Other core configurations and special
constructions, including halogen-free
versions, manufactured upon request.
|
 |
Technical Data
| Conductor cross section |
: |
0.5 mm2 |
1.0 mm2 |
|
|
| Conductor resistance at 20° C max |
|
73.6 |
36.8 Ω/km |
| Insulation resistance min. |
|
100 |
100 m Ω .km |
| Operating capacit. at 800 Hz
max. |
|
1001) |
1001) nF/km |
| Capacitance unbalance max. |
|
1002) |
1002) pF/100 m |
| Crosstald attenuation at 10 kHz
min. |
|
60 |
60 dB/500 m |
| Line attenuation |
|
|
|
| at 1 kHz (guiding value) |
|
1.15 |
0.8 dB/km |
| at 10 kHz (guiding value) |
|
3.0 |
2.1 dB/km |
| Characteristic impedance |
|
|
|
| at 1 kHz (guiding value) |
|
370 |
260 Ω |
| at 10 kHz (guiding value) |
|
130 |
90 Ω |
| Operating voltage (peak value)
max. |
|
600 |
600 V |
| Test voltage |
|
|
|
| core/core |
|
2000 |
2000 V |
| core/screen |
|
2000 |
2000 V |
| Temperature range |
|
|
| Mobile |
|
- 5° C to + 70° C |
| Fixed |
|
-30° C to + 70° C |
| Minimum bending radius |
|
approx. 7.5xcable-Ø |
| Radiation resistance |
|
80 Mrad (80 x 10
6 cJ/kg) |
| Testing: according to DIN VDE
0472 and IEC regulations Flame
test |
|
test class B according
to VDE 0472 part 804 and IEC 332-1 |
| PVC characteristics |
|
self-extinguishing
and flame-retardant |
| |
|
|
|
| |
|
|
|
1) the values may be exceeded
by 20% by cables with up to 4 pairs.
2) 20%
of the values, at least one value up
to 200 pF permitted.
|
 |
Dimensions
| Reference |
Approx.
Outer
Diameter
In mm
|
Copper
Weight
Kg/km
|
Approx.
Cable weight
Kg/km
|
| Part no.
08...
Type
|
No. of conductors
Nominal cross
section mm2
|
| RD-Y
(St)Y |
2x2x0.5
*Bd
|
|
|
|
| |
4x2x0.5
|
|
|
|
| |
8x2x0.5
|
|
|
|
| |
12x2x0.5
|
|
|
|
| |
16x2x0.5
|
|
|
|
| |
20x2x0.5
|
|
|
|
| |
24x2x0.5
|
|
|
|
| |
28x2x0.5
|
|
|
|
| |
32x2x0.5
|
|
|
|
| |
36x2x0.5
|
|
|
|
| |
|
|
|
|
| |
44x2x0.5
|
|
|
|
| |
48x2x0.5
|
|
|
|
| |
52x2x0.5
|
|
|
|
| |
56x2x0.5
|
|
|
|
| |
60x2x0.5
|
|
|
|
| |
64x2x0.5
|
|
|
|
| |
|
|
|
|
| |
96x2x0.5
|
|
|
|
| |
|
|
|
|
| RD-Y
(St)Y |
2x2x1.0*Bd |
|
|
|
| |
4x2x1.0 |
|
|
|
| |
8x2x1.0 |
|
|
|
| |
|
|
|
|
| |
16x2x1.0 |
|
|
|
| |
20x2x1.0 |
|
|
|
| |
|
|
|
|
| |
28x2x1.0 |
|
|
|
| |
32x2x1.0 |
|
|
|
| |
36x2x1.0 |
|
|
|
| |
40x2x1.0 |
|
|
|
| |
44x2x1.0 |
|
|
|
| |
48x2x1.0 |
|
|
|
| |
52x2x1.0 |
|
|
|
| |
|
36.0 |
|
|
| |
|
37.3 |
1215 |
|
| |
64x2x1.0 |
|
1296 |
|
| |
80x2x1.0 |
|
|
|
| |
96x2x1.0 |
46.0 |
|
2885 |
| |
|
|
|
|
* 2 pair laid up as star quad
|
 |
Note
Other core configurations and special constructions, including halogen-free versions, manufactured upon request.
Identification of cores and
pairs
Identification of the
insulation of the cores by different
colours which are repeated in the
same sequence in each bundle.
Identification
of pairs
The pairs are identified
by the basic colours of the insulation.
Basic
colours for pairs
| Pair no. |
Basic
color |
| |
|
a-core and |
b-core |
|
|
Pair 1 |
|
blue |
red |
Pair 2 |
|
grey |
yellow |
Pair 3 |
|
green |
brown |
| Pair 4 |
|
white |
black |
|
|
Bundle : 4 pairs laid up to a bundle
Bundle
identification : each bundle is identified
by one open support spiral with imprinted
numbers.
Method of counting : commencing
at the inner layer with no.1 and
counting successively outwards through
all layers in the same manner.
|
| |
 |
| |